NOTA 48x10kW
Basic Features
-
Structural framework with inner dimensions 5,4*14.7*3m, including raised floor, fire suppression system (Novec1230), access control, air curtain, illumination, inner partition for an airlock, ramp.
-
System of equipment deployment – 24 racks with maximum IT-load 10kW each. Racks are mounted in two rows forming a hot aisle between them.
-
System of cooling based on in-row air conditioners Clever Breeze with 300 kW capacity and the N+1 level of redundancy. It also contains built-in ultrasonic humidity system. To provide uninterruptible performance, cooling conditioners, and humidity system are supplied by UPS.
-
System of uninterruptible power supply with 500kW capacity and N+1 level of redundancy. Time of autonomous work with engineering equipment (conditioner, illumination, access control etc.) is 14 minutes.
-
System of power input and distribution with the monitoring of current power consumption with 2N of redundancy (in each rack there are two rack-PDU connected to UPS via own automatic switches).
-
System of remote control and management.