NOTA 5x7kW
Basic Features
-
Structural frame framework with inner dimensions , 3*6,3*3m, including raised floor, fire suppression system, access control , air curtain, illumination, inner partition for an airlock, ramp
-
System of equipment deployment – 5 racks with maximum IT-load 7kW each
-
System of uninterruptible power supply with 64kW capacity and the N+1 level of redundancy. Time of autonomous work with 51kW of IT-load including engineering equipment (conditioner, illumination, access control etc.) is 15 minutes
-
System of power input and distribution with the monitoring of current power consumption with 2N of redundancy (in each rack there are two rack-power distribution units of power distribution connected to UPS via own automatic switches)
-
System of air conditioning Clever Breeze with 42 kW capacity and the N+1 level of redundancy. To provide uninterruptible cooling conditioning also is supplied by UPS. It is installed under the raised floor , outdoor units are on the front wall of the module
Technical Characteristics of Cooling System
-
Temperature of the cold aisle is +22°C (±2°C)
-
Operational temperatures are from -55°C to +50°C
-
Built-in humidity control system
-
-
The average annual PUE (Power Usage Effectiveness) coefficient is 1,357
-
System of remote control and management