NOTA 24x7kW

Basic Features
  • Structural framework with inner dimensions , 5,4*10,5*3m, including raised floor, fire suppression system (Novec1230), access control , air curtain, illumination, inner partition for an airlock, ramp.

  • System of equipment deployment – 24 racks with maximum IT-load 7kW each. Racks are mounted in two rows forming a hot aisle between them.

  • System of cooling based on in-row air conditioners Clever Breeze with 210 kW capacity and the N+1 level of redundancy. To provide uninterruptible cooling conditioners are also supplied by UPS.

  • System of uninterruptible power supply with the N+1 level of redundancy is installed in a separate module NOTA UPS. Time of autonomous work of IT-equipment including all engineering systems (conditioner, illumination, access control etc.) is 10 minutes. NOTA UPS is euqiped with its own system of climate contol.

  • System of power input and distribution with the monitoring of current power consumption with 2N of redundancy (in each rack there are two rack-PDU connected to UPS via own automatic switches).

  • System of remote control and management.

 